Ampco Engineering Ltd
Unit 2
Mosshill Industrial Estate
Ayr, Scotland, KA6 6BE

Tel: +44(0)7896 236584
Fax: +44(0)1292 619002
Email: sales@ampco.co.uk
          info@ampco.co.uk

Delivering power safely

Ampco are manufacturers of a wide range of hazardous area generators to IECEx and ATEX standards.

Manufacturers of Generators for Hazardous Environments

OFFSHORE GENERATOR EQUIPMENT FOR OIL AND GAS INDUSTRY, ZONE 2 HAZARDOUS AREA - 200KVA

Ex Certification Logos
  • ZONE 2 HAZARDOUS AREA COMPLIANT
  • PRODUCES 200KVA, 480 VAC, 3 PHASE + NEUTRAL, 60HZ
  • OTHER POWER OUTPUTS AVAILABLE

Zone 2 Hazardous Area Generator 200KVA

Operation/Service

Zone 2 Diesel driven generator set mounted in a DNV 2.7-1 certified enclosure producing 200kVA @ 0.8pf, 480VAC, 3 phase + neutral, 60Hz output.

For use in oil, gas and petrochemical industry.

Components

Caterpillar C9 engine rated at 361BHP @ 1800 RPM fitted with an AMPCO Zone 2 generator with electronic control and safety shutdown system, consisting of:

  • Engine over-speed
  • Coolant temperature trip
  • Oil pressure trip
  • Gas detection trip
  • Exhaust temperature trip
  • Trickle charger for unit batteries
  • Battery powered engine start
  • Electrical output monitoring system
  • Electrical isolator switch
  • Electrical output connection panel

Control Panels

The engine control panels accommodate all engine and generator controls and indicators. This includes:

  • MCCB
  • Over/under voltage protection
  • Over/under frequency protection
  • Meters – voltage, Hz, amps
  • Start and Stop Switch
  • Emergency Stop
  • Engine Speed
  • Engine oil pressure trip light
  • Engine exhaust temperature trip light
  • Engine coolant temperature trip light
  • Engine data display

Fuel Tank

  • 1500L Fuel tank capacity
  • During periods of 100% operation this fuel tank capacity allows for a run time of 22 hours

Safety/Environmental

  • Bunding for containment of fluids should there be any leaks or spills
  • Drain Points
  • Guarding supplied around all moving parts

Standards/Certification

IECEx
2014/34/EU ATEX Equipment Directive
2006/42/EC Machinery Directive
DNV 2.7-1 Container IEE Wiring Regulations
2000/14/EC Noise emission in the environment by equipment for use outdoors as amended by 2005/88/EC

Mass

Maximum Gross: 16,000kg Actual Weight: 13,400kg Frame Tare Weight: 2,600kg

Dimensions (LxWxH)

LENGTH: 5,172 mm

WIDTH: 2,438 mm

HEIGHT: 3,148 mm

Design/ambient Temperature

Minimum: -20˚C

Maximum: +45˚C

Zone 2 Generator Instrumentation and Control Panels