Ampco Engineering Ltd
Unit 2
Mosshill Industrial Estate
Ayr, Scotland, KA6 6BE
Tel: +44(0)7896 236584
Fax: +44(0)1292 619002
Email: sales@ampco.co.uk
info@ampco.co.uk
Ampco are manufacturers of a wide range of hazardous area generators to IECEx and ATEX standards.
Manufacturers of Generators for Hazardous Environments
OFFSHORE GENERATOR EQUIPMENT FOR OIL AND GAS INDUSTRY, ZONE 2 HAZARDOUS AREA - 200KVA
- ZONE 2 HAZARDOUS AREA COMPLIANT
- PRODUCES 200KVA, 480 VAC, 3 PHASE + NEUTRAL, 60HZ
- OTHER POWER OUTPUTS AVAILABLE
Operation/Service
Zone 2 Diesel driven generator set mounted in a DNV 2.7-1 certified enclosure producing 200kVA @ 0.8pf, 480VAC, 3 phase + neutral, 60Hz output.
For use in oil, gas and petrochemical industry.
Components
Caterpillar C9 engine rated at 361BHP @ 1800 RPM fitted with an AMPCO Zone 2 generator with electronic control and safety shutdown system, consisting of:
- Engine over-speed
- Coolant temperature trip
- Oil pressure trip
- Gas detection trip
- Exhaust temperature trip
- Trickle charger for unit batteries
- Battery powered engine start
- Electrical output monitoring system
- Electrical isolator switch
- Electrical output connection panel
Control Panels
The engine control panels accommodate all engine and generator controls and indicators. This includes:
- MCCB
- Over/under voltage protection
- Over/under frequency protection
- Meters – voltage, Hz, amps
- Start and Stop Switch
- Emergency Stop
- Engine Speed
- Engine oil pressure trip light
- Engine exhaust temperature trip light
- Engine coolant temperature trip light
- Engine data display
Fuel Tank
- 1500L Fuel tank capacity
- During periods of 100% operation this fuel tank capacity allows for a run time of 22 hours
Safety/Environmental
- Bunding for containment of fluids should there be any leaks or spills
- Drain Points
- Guarding supplied around all moving parts
Standards/Certification
IECEx
2014/34/EU ATEX Equipment Directive
2006/42/EC Machinery Directive
DNV 2.7-1 Container IEE Wiring Regulations
2000/14/EC Noise emission in the environment by equipment for use outdoors as amended by 2005/88/EC
Mass
Maximum Gross: 16,000kg Actual Weight: 13,400kg Frame Tare Weight: 2,600kg
Dimensions (LxWxH)
LENGTH: 5,172 mm
WIDTH: 2,438 mm
HEIGHT: 3,148 mm
Design/ambient Temperature
Minimum: -20˚C
Maximum: +45˚C
Zone 2 Generator Instrumentation and Control Panels