Delivering power safely

Ampco are manufacturers of a wide range of hazardous area generators to IECEx and ATEX standards.

Manufacturers of Generators for Hazardous Environments

ZONE 2 GENERATOR IECEX ATEX 20-150KVA

Ex Certification Logos
  • ZONE 2 HAZARDOUS AREA COMPLIANT
  • MODELS PRODUCE 20-150KVA, 400/480 VAC, 3 PHASE + NEUTRAL, 50/60HZ


ZONE 2 GENERATOR IECEX ATEX 20-150KVA

Operation/Service

Zone 2 Diesel driven generator set producing 20-150kVA @ 0.8pf, 400/480VAC, 3 phase + neutral, 50/60Hz output. For use in oil, gas and petrochemical industry during operations and decommission.

Components

Zone 2 engine fitted with an AMPCO Zone 2 generator with electronic control and safety shutdown system, consisting of:

  • Engine over-speed
  • Coolant temperature trip
  • Oil pressure trip
  • Gas detection trip
  • Exhaust temperature trip
  • Trickle charger for unit batteries
  • Battery powered engine start
  • Electrical output monitoring system
  • Electrical isolator switch
  • Electrical output connection panel

Control Panels

The engine control panels accommodate all engine and generator controls and indicators. This includes:

  • MCCB
  • Over/under voltage protection
  • Over/under frequency protection
  • Meters – voltage, Hz, amps
  • Start and Stop Switch
  • Emergency Stop
  • Engine Speed
  • Engine oil pressure trip light
  • Engine exhaust temperature trip light
  • Engine coolant temperature trip light
  • Engine data display

Fuel Tank

  • Fuel tank capacity
  • During periods of 100% operation this fuel tank capacity allows for a run time of 36 hours

Safety/Environmental

  • Bunding for containment of fluids should there be any leaks or spills
  • Drain Points
  • Guarding supplied around all moving parts

Standards/Certification

IECEx
2014/34/EU ATEX Equipment Directive
2006/42/EC Machinery Directive
DNV 2.7-1 Container
IEE Wiring Regulations
2000/14/EC Noise emission in the environment by equipment for use outdoors as amended by 2005/88/EC

Design/ambient Temperature

Minimum: -20˚C

Maximum: +45˚C

Zone 2 Generator Instrumentation and Control Panel

Zone 2 Generator Instrumentation and Control Panels

Zone 2 Generator Model Details

Model

Output (kVA)

Length (mm)

Width (mm)

Height (mm)

Weight (kg)

DGN020

20

2800

2300

2000

2100

DGN040

40

3000

2400

2200

2500

DGN060

60

3400

2400

2300

3000

DGN080

80

3700

2400

2500

3400

DGN100

100

3900

2400

2700

3700

DGN150

150

4100

2400

2900

3900